660
35 CPU MODULE BUILT-IN ANALOG FUNCTION
35.6 Function (PID Control Via Parameter)
Setting and program examples
This section shows parameter setting examples and program examples when using the heating-cooling PID control function.
Setting example 2
When "Control mode" is "Standard PID control mode", after auto tuning starts and ends completely, PID control using the
obtained control parameters is performed.
System configuration
Operation example
0V
COM0
Y0
FX5-4AD-TC-ADP
Y1
24V X0 X1
FX5U-32MT/ES
L1+
L1-
X0: PID control execution command
X1: Auto tuning used/not used
Y0: Error indication
Y1: Control output
Parameter settings
24VDC
Temperature tank
Electric
heater
Temperature sensor
(thermocouple)
Heater
Measured value (PV)
During auto tuning During PID control
Target value (SV) = 50.0ºC
1st cycle 2nd cycle
Time
ON
OFF
ON
OFF
During auto tuning (when the upper limit output limiter is 90%)
Output value (MV) = 90% Output value (MV) = 90% Output value (MV) = 0%
Control output
(Y1)
Output value (MV) / 100 ×
Control output cycle = 4.5s
Output value (MV) / 100 ×
Control output cycle = 4.5s
Control output cycle
(50 × 100ms = 5s)
Control output cycle
(50 × 100ms = 5s)
Control output cycle
(50 × 100ms = 5s)
During PID control
Output value (MV) = 60% Output value (MV) = 30% Output value (MV) = 40%
Control output
(Y1)
Output value (MV) / 100 ×
Control output cycle = 3.0s
Output value (MV) / 100 ×
Control output cycle = 1.5s
Output value (MV) / 100 ×
Control output cycle = 2.0s
Control output cycle
(50 × 100ms = 5s)
Control output cycle
(50 × 100ms = 5s)
Control output cycle
(50 × 100ms = 5s)