35 CPU MODULE BUILT-IN ANALOG FUNCTION
35.3 Functions (Analog Input)
585
35
Warning output function
The warning output flag for the corresponding channel turns ON when the digital operation value is equal to or greater than
the process alarm upper upper limit value, is equal to or lower than the process alarm lower lower limit value, or falls within the
warning output range.
Corresponding devices
The devices which are used by the warning output function are listed below.
Setting methods
The procedure to use the warning output function is described below.
1. Disable the warning output setting (process alarm).
2. Set the upper limit and lower limit values for the process alarm.
Four levels of values from the process alarm upper upper limit value to the process alarm lower lower limit value can be set for
each channel that uses the warning output function (process alarm).
3. Enable the warning output setting (process alarm).
Name CH1 CH2
Warning output flag (process alarm upper limit) SM6031 SM6071
Warning output flag (process alarm lower limit) SM6032 SM6072
Warning output setting (process alarm) SM6033 SM6073
A/D conversion alarm clear request SM6057 SM6097
A/D conversion alarm flag SM6058 SM6098
Process alarm upper upper limit value SD6031 SD6071
Process alarm lower upper limit value SD6032 SD6072
Process alarm upper lower limit value SD6033 SD6073
Process alarm lower lower limit value SD6034 SD6074
A/D conversion latest alarm code SD6058 SD6098
Name Allowable setting range Default value
Warning output setting (process alarm) 0: Enabled 1: Disabled
1: Disabled
Name Allowable setting range Default value
Process alarm upper upper limit value -32768 to +32767
(Upper-upper limit valueUpper-
lower limit valueLower-upper limit
valueLower-lower limit value)
0
Process alarm lower upper limit value
Process alarm upper lower limit value
Process alarm lower lower limit value