25 HIGH-SPEED INPUT/OUTPUT FUNCTION
25.1 High-speed Counter Function
257
25
High-speed comparison table
The high-speed comparison table is explained below.
Used to set high-speed comparison table for high-speed counters.
Parameter setting
Sets match output setting for high-speed counters.
CPU module
Navigation window [Parameter] [Module model name] [Module Parameter] [High Speed I/O] "Input
Function" "High Speed Counter" "Detailed Setting" "High Speed Compare Table"
Window
Displayed items
High-speed pulse input/output module
Add the high-speed pulse input/output module.
Navigation window [Parameter] [Module Information] Right-click Add New Module
After adding the high-speed pulse input/output module, make settings on the screen displayed from the following operation.
Navigation window [Parameter] [Module Information] [1 to 16 (high-speed pulse input/output module)]
[Module Parameter] "Input Function" "High Speed Counter" "Detailed Setting" "High Speed Compare Table"
Item Description Setting range Default
Counter CH Set the counter CH of coincidence output target. Disable, CH1 to CH8 Disable
Comparison Type Set comparison type. Set
•Reset
Self Reset
Band Area Comparison
Set
Output Destination Device Sets output destination device for output comparison results of
comparison value 1 and comparison value 2.
Bit device (Y, M), Interrupt pointer (I16 to
I23)
Comparison Value 1
Specification Method
Sets the specification method of comparison value 1. Direct Specification
Indirect Specification
Direct
Specification
Comparison Value 1 Direct Sets value (comparison value 1) to be compared with current value
of high-speed counter. (When direct specification is selected)
-2147483648Comparison value
1+2147483647
0
Comparison Value 1
Indirect
Sets device (comparison value 1) to be compared with current value
of high-speed counter. (When indirect specification is selected)
Word device (D, R)
Comparison Value 2
Specification Method
If band comparison is set to comparison type, sets the specification
method of comparison value 2.
Direct Specification
Indirect Specification
Comparison Value 2 Direct If band comparison is set to comparison type, sets value
(comparison value 2) to be compared with current value of high-
speed counter. (When direct specification is selected)
Comparison value 1Comparison value
22147483647
Comparison Value 2
Indirect
If band comparison is set to comparison type, sets device
(comparison value 2) to be compared with current value of high-
speed counter. (When indirect specification is selected)
Word device (D, R)