Appendix 2 Special Register List
Scan information
The special registers for scan information are shown below.
No. Name Description Compatible CPU module R/W
FX5S FX5UJ FX5U/
FX5UC
SD518 Initial scan time (ms) The initial scan time is stored into SD518 and
SD519 (it is measured in increments of s).
SD518: stores a value in the ms place (storage
range: 0 to 65535)
SD519: stores a value in the s place (storage
range: 0 to 999)
This register is cleared to 0 when the mode
transfers from STOP to RUN mode.
R
SD519 Initial scan time (s) R
SD520 Current scan time (ms) The current scan time is stored into SD520
and SD521 (it is measured in increments of
s).
SD520: stores a value in the ms place (storage
range: 0 to 65535)
SD521: stores a value in the s place (storage
range: 0 to 999)
Example: If the current scan time is 23.6ms, the
following values are stored:
SD520 = 23
SD521 = 600
This register is cleared to 0 when the mode
transfers from STOP to RUN mode.
R
SD521 Current scan time (s) R
SD522 Minimum scan time (ms) The minimum value of the scan time other
than that of the initial execution program is
stored into SD522 and SD523 (it is measured
in increments of s).
SD522: stores a value in the ms place (storage
range: 0 to 65535)
SD523: stores a value in the s place (storage
range: 0 to 999)
This register is cleared to 0 when the mode
transfers from STOP to RUN mode.
R
SD523 Minimum scan time (s) R
SD524 Maximum scan time (ms) The maximum value of the scan time other
than that of the initial execution program is
stored into SD524 and SD525 (it is measured
in increments of s).
SD524: stores a value in the ms place (storage
range: 0 to 65535)
SD525: stores a value in the s place (storage
range: 0 to 999)
This register is cleared to 0 when the mode
transfers from STOP to RUN mode.
R
SD525 Maximum scan time (s) R
SD526 END processing time (ms) The time period from completion of a scan
program until start of the next scan is stored
into SD526 to SD527 (it is measured in
increments of s).
SD526: stores a value in the ms place (storage
range: 0 to 65535)
SD527: stores a value in the s place (storage
range: 0 to 999)
This register is cleared to 0 when the mode
transfers from STOP to RUN mode.
R
SD527 END processing time (s) R
SD528 Constant scan waiting time (ms) The waiting time specified in the constant
scan setting process is stored into SD528 and
SD529 (it is measured in increments of s).
SD528: stores a value in the ms place (storage
ra
nge: 0 to 65535)
SD529: stores a value in the s place (storage
range: 0 to 999)
This register is cleared to 0 when the mode
transfers from STOP to RUN mode.
R
SD529 Constant scan waiting time (s) R