242
25 HIGH-SPEED INPUT/OUTPUT FUNCTION
25.1 High-speed Counter Function
High-speed pulse input/output module
of each input is the head input number for high-speed pulse input/output module.
A: Input A phase
B: Input B phase (direction switch input is however employed in the case of 1-phase 1-count [H/W])
P: Input external preset
E: Input external enable
The high-speed pulse input/output module channel numbers are assigned as described below. From nearest
to the CPU module, the high-speed pulse input/output modules are ordered as the first module, second
module, etc.
High-speed pulse input/output module first module: CH9, CH10
High-speed pulse input/output module second module: CH11, CH12
High-speed pulse input/output module third module: CH13, CH14
High-speed pulse input/output module fourth module: CH15, CH16
Input assignment-wise / maximum frequency for high-speed counters
Input assignment-wise maximum frequency for high-speed counters is as follows.
FX5S/FX5UJ CPU module
CH High-speed
counter type
X X+1 X+2 X+3 X+4 X+5 X+6 X+7
CH9,
CH11,
CH13,
CH15
1-phase 1-count (S/W) A P E
1-phase 1-count (H/W) A B P E
1-phase 2-count A B P E
2-phase 2-count A B P E
CH10,
CH12,
CH14,
CH16
1-phase 1-count (S/W) A P E
1-phase 1-count (H/W) A B P E
1-phase 2-count A B P E
2-phase 2-count A B P E
CH9 to
CH16
Internal clock Not used
CH High-speed counter
type
X0 X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 X16 X17 Maximum
frequency
CH1 1-phase 1-count (S/W) A P E 100 kHz
1-phase 1-count (H/W) A B P E 100 kHz
1-phase 2-count A B P E 100 kHz
2-phase 2-count [1 edge
count]
A B P E 100 kHz
2-phase 2-count [2 edge
count]
A B P E 50 kHz
2-phase 2-count [4 edge
count]
A B P E 25 kHz
CH2 1-phase 1-count (S/W) A P E 100 kHz
1-phase 1-count (H/W) A B P E 100 kHz
1-phase 2-count A B P E 10 kHz
CH3 1-phase 1-count (S/W) A P E 10 kHz
1-phase 1-count (H/W) A B P E 10 kHz
1-phase 2-count A B P E 10 kHz