244
25 HIGH-SPEED INPUT/OUTPUT FUNCTION
25.1 High-speed Counter Function
■FX5U-32M, FX5UC-32M
• X6 to X17 are input frequencies up to 10 kHz, regardless of maximum frequency value.
• Preset input and Enable Input are input frequencies up to 10 kHz, regardless of maximum frequency value.
CH High-speed counter
type
X0 X1 X2 X3 X4 X5 X6 X7 X10 X11 X12 X13 X14 X15 X16 X17 Maximum
frequency
CH1 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz
CH2 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz
CH3 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 200 kHz
1-phase 2-count A B P E 200 kHz
2-phase 2-count [1 edge
count]
A B P E 200 kHz
2-phase 2-count [2 edge
count]
A B P E 100 kHz
2-phase 2-count [4 edge
count]
A B P E 50 kHz
CH4 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 10 kHz
1-phase 2-count A B P E 10 kHz
2-phase 2-count [1 edge
count]
A B P E 10 kHz
2-phase 2-count [2 edge
count]
AB P E 5 kHz
2-phase 2-count [4 edge
count]
A B P E 2.5 kHz
CH5 1-phase 1-count (S/W) A P E 200 kHz
1-phase 1-count (H/W) A B P E 10 kHz
1-phase 2-count A B P E 10 kHz
2-phase 2-count [1 edge
count]
ABPE 10 kHz
2-phase 2-count [2 edge
count]
ABPE 5 kHz
2-phase 2-count [4 edge
count]
ABPE 2.5 kHz