36
1 PROGRAM EXECUTION
1.4 Execution Type of Program
Trigger setting
Use the event execution type detail setting.
Navigation window [Parameter] [Module model name] [CPU Parameter] "Program Setting"
When "Clear Output and Current Value of Timer" is enabled together with "ON of Bit Data (TRUE)" or
"Passing Time", the current values of the output (Y) and timer (T) of this program can be cleared at the first
execution turn of this program that comes after the trigger turns OFF.
"Program Setting" window
1. Click "Detailed Setting" on the Program Setting.
"Detailed Setting" window
2. Select the program name and set the execution type
to "Event".
3. Click "Detailed Setting Information".
"Event Execution Type Detailed Setting" window
4. Set the trigger type to execute the event execution
type program.
Item Description Setting range Default
Interruption Occurrence Sets the interrupt pointer used as the trigger. I0 to I23, I50 to I177
ON of Bit Data (TRUE) Sets the device used as the trigger. Page 35 Bit data ON (TRUE)
Clear Output and Current Value of
Timer
Sets that the current values of the output (Y), and
timer (T) used in this program are cleared at the
execution turn of the event execution type program
that comes after the specified bit data is OFF.
• Do Not Clear
• Clear
Do Not Clear
Passing Time Unit Sets the time passed. • When "ms" is selected: 1 to 65535ms (in
units of 1ms)
• When "s" is selected: 1 to 65535s (in units of
1s)
Clear Output and
Current Value of
Timer
Sets that the current values of the output (Y), and
timer (T) used in this program are cleared at the
execution turn of the event execution type program
that comes after the specified time passes.
• Do Not Clear
• Clear