EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-F FX5 - Page 605

Mitsubishi Electric MELSEC iQ-F FX5
958 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35 CPU MODULE BUILT-IN ANALOG FUNCTION
35.5 Function (PID Control Via Instruction)
603
35
Upper and lower limits for output value
When the upper and lower limit settings of the output value are valid, the output value is as shown in the chart. The upper limit
and lower limit of the output value can moderate the increase of the integral item in the PID control.
When using the upper limit and lower limit of the output value, make sure to set (s3)+1, b2 to OFF.
Set item Description/Setting range
Operation setting (s3)+1: b2 Output variation alarm Make sure to set it to OFF
(s3)+1: b5 Output value upper/lower limit setting ON: Used
OFF: Not used
Output value upper limit
Output value lower limit
Time
(s3)+22
Output value (MV)
(s3)+23
These values are not output
These values are not output
When the upper limit and
lower limit of output value are set
When the upper limit and
lower limit of output value are not set

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-F FX5

Related product manuals