70
4 DEVICES
4.6 File Register (R/ER)
Data batch writing function
All the value registered to the device memory in the project of GX Works3 (extended file register (ER)) can be written to the
extended file register (ER) in the SD memory card in a batch.
[Online] [Write to PLC]
Window
Check the "Extended File Register" box under SD memory card, execute write, and the value of the device memory in the
project of GX Works3 (extended file register (ER)) will be stored to the extended file register (ER) in the SD memory card.
All the points (32768 points) of the device memory in the project of GX Works3 are written to the extended file register (ER) in
the SD memory card without depending on the user's device point setting of the file register (R). (Page 84 Device Setting)