722
APPX
Appendix 2 Special Register List
SD81 to
SD111
Detailed information 1 (5) System configuration information
(6) Number of times information
(7) Time information
R
SD112 Detailed information 2
information category
Detailed information 2 information category code is stored.
The following codes are stored into the information category code.
0: N/A
2: Drive number and file name
3: Annunciator number
4: Parameter information
5: System configuration information
R
No. Name Description Compatible CPU module R/W
FX5S FX5UJ FX5U/
FX5UC
With or without specification
b15
b15 b0b8 b7
b1 b0b2b3b4b5b6b7
SD81
SD82
SD83
SD84
SD85
SD86
Function No.
Module position
Head Y No.
÷
8Head X No.
÷
8
Free (Fixed to 0)
Intelligent module No.
Network No.
Station No.
Head X No.
Head Y No.
Module position
Function No.
Intelligent module No.
Free
Network No.
Station No.
Module position
CPU module : 0H
Extension module 1 to 16 : 1H to 10H
Built-in RS-485
: 41H
Built-in analog : 42H
Built-in USB : 43H
Expansion board : 60H
Expansion adapter 1 to 6: 71H to 76H
Function No.
System/Sequence operation
: 0
Analog input : 1
Analog output : 2
Positioning, PWM : 10
High-speed counter,
Pulse width measurement : 20
Serial communication
: 30
Either XY head No. or intelligent
module No. is set.
With or without specification
Number of times (set value) L
Number of times (set value) H
Number of times (actual measurement value) L
Number of times (actual measurement value) H
b15
b15
b1 b0
b0
b2
SD81
SD85
SD84
SD83
SD82
Number of times
(set value)
Number of times
(actual measurement
value)
With or without specification
b15 b1b0b2b3b4
SD81
SD82
SD83
SD84
SD85
Time (set value) (
μ
s)
Time (set value) (ms)
Time (actual measurement value) (ms)
Time (actual measurement value) (
μ
s)
Time (set value) (ms)
Time (set value) (
μ
s)
Time (actual
measurement value)
(ms)
Time (actual
measurement value)
(
μ
s)
b15 b0
Not used (fixed to 0) Information category code