866
APPX
Appendix 8 How to Use CPU Module Logging Configuration Tool
Logging status and operation
The following procedure is to execute or stop the data logging. Also the data logging status can be checked through this
procedure.
Operating procedure
1. Open the "Logging Status and Operation" window.
[Online] [Logging Status and Operation]
2. Specify the target memory (either data memory or SD memory card) where the effective setting data is stored.
3. Select the checkbox corresponding to the setting number to be executed (Multiple selection possible)
4. Start the data logging by clicking the [Start] button. (When multiple items are selected, they are executed
simultaneously.)
5. To suspend data logging, click the [Pause] button. To stop data logging, click the [Stop] button. (When multiple items are
selected, they are executed simultaneously.)
The data logging cannot be started even when writing the setting and turning power off and on or resetting.
Be sure to click the [Start] button to start data logging.
With regards to the trigger logging, the data logging setting registration attempt fails if the trigger condition is
satisfied.
It takes a certain time to stop or suspend the data logging after either of these commands is issued by CPU
Module Logging Configuration Tool (because the data logging is not stopped or suspended unless the data
stored in the internal buffer data has been transferred into the SD memory card in response to these
commands).
There may be a case where a time-out error occurs and the data logging is suspended after CPU Module
Logging Configuration Tool starts the logging.
Window