194
(2) Using equal assignment
The link device I/O range can be equally assigned between the I/O master and other stations. (LX/LY Setting(1)
only)
1. Open the "Assignment the CC IE Control Network Range" window in the programming tool.
( Page 183, Section 6.3)
2. Click the button.
3. Configure settings with reference to the description below.
4. Click the button.
Ex.
When assigning LX/LY1000 to 15FF (1536 points) equally to the I/O range between the I/O master station
and station No.2 to No.4
5. Equal assignment is done in "LX/LY Setting(1)" of "Assignment the CC IE Control Network
Range".
Item Description
X/Y Equal
Assignment
Start Station
Set the start station.
(Setting range for Universal model QCPU: 1 to 120, Default: None)
(Setting range for other than Universal model QCPU: 1 to 64, Default: None)
End Station
Set the end station.
(Setting range for Universal model QCPU: 1 to 120, Default: None)
(Setting range for other than Universal model QCPU: 1 to 64, Default: None)
Start No.
Set the start number of the LX/LY for equal assignment.
(Setting range: 0000
H
to 1FF0
H
, Default: None)
Total Points
Assigned
Set the total points of LX/LY, which are to be assigned equally.
(Setting range: 16 to 8192, Default: None)