CHAPTER 9 DEDICATED INSTRUCTIONS
9
9.7 J(P)/G(P).REQ (Remote RUN/STOP)
*1 The setting side is as shown below.
User: Before execution of the link dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the link dedicated instruction.
*2 Data is not stored when Completion status ((S1)+1) is "Channel busy (Dedicated instruction) (error code: E26C
H
)".
The number of resends ((S1)+7) must be set every time an instruction is executed.
(b) Request data (All set by the user)
(S1)+12
to
(S1)+15
Clock data on
error completion
Clock data on error completion are stored in BCD format. Data is
stored only when 1 is set in the bit 7 of Error completion type
((S1)+0). Note that the stored value will not be cleared even after the
dedicated instruction is completed.
When the target station is QnACPU, "00
H
" is stored in the Year field
(first two digits of the year).
—System
(S1)+16
Error-detected
network No.
*2
Network No. of the station, where an error was detected, is stored.
Data is stored only when 1 is set in the bit 7 of Error completion type
((S1)+0). Note that the stored value will not be cleared even after the
dedicated instruction is completed.
1 to 239: Network No.
—System
(S1)+17
Error-detected
station No.
*2
Station No. of the station, where an error was detected, is stored.
Data is stored only when 1 is set in the bit 7 of Error completion type
((S1)+0). Note that the stored value will not be cleared even after the
dedicated instruction is completed.
1 to 120: Station No.
—System
Device Item Setting data
Remote
RUN
Remote
STOP
(S2)+0 Request type
0010
H
: When station No. is specified in (S1)+5
0030
H
: When all stations or a group is specified in (S1)+5
(S2)+1 Sub-request type
0001
H
: Remote RUN
0002
H
: Remote STOP
(S2)+2 Operation mode
Specify whether to forcibly execute remote RUN/STOP or not.
The forced execution is a function that forces a station which has
stopped by remote STOP to RUN remotely from another station.
• For remote RUN
0001
H
: No forced execution
0003
H
: Forced execution
• For remote STOP
0003
H
(Fixed)
Device Item Setting data Setting range
Setting
side
*1
(S1)+12
(S1)+13
(S1)+14
(S1)+15
Month (01
H to 12H)
Hour (00
H to 23H)
Second (00
H to 59H)
Day (01
H to 31H)
Minute (00
H to 59H)
00
H (Sun.) to 06H (Sat.)
Day of week (00
H to 06H)
Year (00
H
to 99
H
) First 2 digits
Year (00
H
to 99
H
) Last 2 digits
b15 b8 b7to b0to