378
: Set —: Not set
(c) Response data (all set by the user)
When "all stations or a group (FF
H
or 81
H
to A0
H
)" is specified in Target station No. ((S1)+5), no response data
will be stored.
: Stored —: Not stored
● Remote RUN/STOP is available when the RUN/STOP switch of the target station CPU is set to "RUN".
● Remote RUN/STOP is not executable when system protect is applied to the target station CPU.
● When the target station CPU has been already in remote STOP/PAUSE state by a request from another station, it cannot
enter RUN mode if Mode ((S2+2) is "No forced execution (0001
H
)".
● If the target station CPU, for which remote STOP was performed, is reset, the remote STOP information is erased.
(S2)+3 Clear mode
Specify the CPU module device status for the case of remote RUN.
0000
H
: Do not clear
(Note that the local devices are cleared.)
0001
H
: Clear (excluding the latch range)
0002
H
: Clear (including the latch range)
Clear mode ((S2)+3) allows specification of the CPU module device
clear (initialization) process at the start of CPU module operation
activated by remote RUN.
After the CPU module clears device data, it enters the RUN status
according to the setting of "Device Initial Value" in the "PLC File" tab
of the PLC parameter in the programming tool.
—
Device Item Setting data
Remote
RUN
Remote
STOP
(D1)+0 Request type
0090
H
: When station No. is specified in (S1)+5
(D1)+1 Sub-request type
0001
H
: Remote RUN
0002
H
: Remote STOP
Device Item Setting data
Remote
RUN
Remote
STOP