9.10 JP/GP.RECV (Data Reception from Programmable Controllers on Other Stations)
(c) RECV instruction settings
Control data settings for the RECV instruction are shown below.
Device Item Set value
(S1)+0 D370 Error completion type
0080
H
(Clock data at the time of error completion is
set.)
(S1)+1 D371 Completion status
—
(Set by the system, no setting required)
(S1)+2 D372 Own station channel 5
(S1)+3 D373 Channel used by sending station
—
(Set by the system, no setting required)
(S1)+4 D374 Network No. of sending station
(S1)+5 D375 Sending station No.
(S1)+6 D376 (Unused) 0
(S1)+7 D377 (Unused) 0
(S1)+8 D378 Arrival monitoring time 0 (10 seconds)
(S1)+9 D379 Receive data length
—
(Set by the system, no setting required)
(S1)+10 D380 (Unused) 0
(S1)+11 D381 Clock set flag
—
(Set by the system, no setting required)
(S1)+12 to
(S1)+15
D382 to D385 Clock data on error completion
(S1)+16 D386 Error-detected network No.
(S1)+17 D387 Error-detected station No.