491
CHAPTER 9 DEDICATED INSTRUCTIONS
9
9.20 J(P)/G(P).RIWT (Data Write to Programmable Controllers on Target Station)
(b) Access code/Attribute code
*1 Devices other than the above are not accessible.
For access to a bit device, specify 0 or multiples of 16.
*2 When the target station is other than the CC-Link IE Controller Network module, refer to the manual for the target station
for the access and attribute codes.
*3 The extended data register of address D65536 or higher, and the extended link register of address W10000 or higher
cannot be specified.
The Arrival monitoring time and Number of resends are specified in the following link special register (SW). ( Page
584, Appendix 2)
• Arrival monitoring time (RIRD/RIWT instruction) (SW0009)
• Number of resends (RIRD/RIWT instruction) (SW000B)
Device contents
*1
Name
Device type
Unit
Access code
*2
Attribute code
*2
Bit Word
Input relay X Hexadecimal
01
H
05
H
Output relay Y Hexadecimal
02
H
Internal relay M Decimal
03
H
Latch relay L Decimal
83
H
Link relay B Hexadecimal
23
H
Timer (contact) T Decimal
09
H
Timer (coil) T Decimal
0A
H
Timer (present value) T Decimal
0C
H
Retentive timer (contact) ST Decimal
89
H
Retentive timer (coil) ST Decimal
8A
H
Retentive timer (present value) ST Decimal
8C
H
Counter (contact) C Decimal
11
H
Counter (coil) C Decimal
12
H
Counter (present value) C Decimal
14
H
Data register
*3
DDecimal
04
H
Link register
*3
W Hexadecimal
24
H
File register R Decimal
84
H
Link special relay SB Hexadecimal
63
H
Link special register SW Hexadecimal
64
H
Special relay SM Decimal
43
H
Special register SD Decimal
44
H