EasyManua.ls Logo

Mitsubishi GOT1000 GT15 - Page 245

Mitsubishi GOT1000 GT15
622 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.1 Display Settings
11.1.1 Display setting functions
11 - 4
9
UTILITY FUNCTION
10
COMMUNICATION
INTERFACE
SETTING
11
DISPLAY AND
OPERATION
SETTINGS
12
CLOCK SETTINGS
AND BATTERY
STATUS DISPLAY
13
FILE DISPLAY AND
COPY
14
GOT SELF CHECK
15
CLEANING OF
DISPLAY SECTION
16
MAINTENANCE
TIME NOTIFICATION
SETTING
(3) Screen save backlight
When [Screen save backlight] is set to [ON], using the system information function
(Backlight OFF output signal) can switch the backlight OFF from the controller.
When [Screen save backlight] is set to [OFF], the above signal has no effect on
the screen save backlight.
• GT Designer3 Version1 Screen Design Manual (Fundamentals)
(4.6 System Information Setting)
• GT Designer2 Version
Screen Design Manual
(3.6 Setting System Information)
(4) Display control by human sensor (Specific to GT1595-X, GT1585V-S, GT1585-S)
The human sensor is a function that releases the GOT from the screen saving
mode without the necessity to touch the GOT.
This function releases the GOT from the screen saving mode when the operator
has come closer to the GOT.
Refer to the following manual for the Human Sensor Detection Signal (System
Signal 2-1.b5).
• GT Designer3 Version1 Screen Design Manual (Fundamentals)
(4.6 System Information Setting)
• GT Designer2 Version
Screen Design Manual
(3.6 Setting System Information)
(5) When setting the human sensor to invalid (Specific to GT1595-X, GT1585V-S,
GT1585-S)
Even if setting the human sensor to invalid by the utility, the Human Sensor
Detection Signal (System Signal 2-1.b5) turns ON when the human sensor
detects human movement.
Unintended operation may result, therefore, if controlling the Forced Screen Saver
Enable Signal (System Signal 1-1.b1) and Human Sensor Detection Signal
associating them with each other by a sequence program, etc.
When setting the human sensor to invalid, review the related sequence program,
etc.
When there is no operator around the GOT for the time set as "Sensor OFF delay", the "Human
Sensor Detection Signal" turns OFF.
When the time set as the "Screen save time" elapses after the "Human Sensor Detection Signal"
turns OFF, the GOT enters the screen saving mode.
ON
OFF
Operator motion
[Sensor detect level]
Human Sensor
Detection Signal
[System Signal 2-1.b5]
Approach Go away Approach Go away
[Sensor
off delay]
Screen saving
Screen saving mode released
Screen saving
mode active
[Screen save time]
[Sensor
off delay]
[Sensor detect time]

Table of Contents