3.3 Power Supply Specifications
3.3.1 For GOTs powered from the 100 to 240VAC power supply
3 - 19
1
OVERVIEW
2
SYSTEM 
CONFIGURATION
3
SPECIFICATIONS
4
PART NAME AND 
SETTINGS
5
EMC AND LOW 
VOLTAGE 
DIRECTIVE
6
INSTALLATION
7
WIRING
8
OPTION
3.3 Power Supply Specifications
The following describes the power supply specifications for the GT15.
3.3.1 For GOTs powered from the 100 to 240VAC power supply
3.3.2 For GOTs powered from the 24VDC power supply
Operation at momentary failure
• If an instantaneous power failure occurs in the power supply and continues 
for more than the permissible period, the GOT will be reset.
• Make sure to power on the unit more than 5 seconds after power-off.
 
3.3.1 For GOTs powered from the 100 to 240VAC power supply
 
Item
Specifications
GT1595-XTBA
GT1585V-STBA,
GT1585-STBA
GT1575V-STBA, GT1575-
STBA, GT1575-VTBA, 
GT1575-VNBA, GT1572-
VNBA, GT1565-VTBA, 
GT1562-VNBA
Input power supply voltage 100 to 240VAC (+10% -15%)
Input frequency 50/60Hz   5%
Input max. apparent power 110VA (maximum load)
Power consumption 56W or less 41W or less 39W or less
At backlight off 30W or less 28W or less
Inrush current
50A or less (4ms) 
(maximum load)
45A or less (4ms) 
(maximum load)
40A or less (4ms) 
(maximum load)
Allowable momentary power 
failure time
20ms or less (100VAC or more)
Noise immunity
1,500Vp-p noise voltage, 1µs noise width (when measuring with a noise simulator 
under 25 to 60Hz noise frequency)
Dielectric withstand voltage 1500VAC for 1 minute across power terminals and earth
Insulation resistance
10M  or more across power terminals and earth by a 500V DC insulation resistance 
tester
Applicable wire size
0.75 to 2 [mm
2
]
Applicable solderless terminal
Solderless terminal for M3 screw  RAV1.25-3, V2-S3.3, V2-N3A, 
FV2-N3A
Applicable tightening torque 
(Terminal block terminal screw)
0.5 to 0.8 [N•m]