14 - 32
14.8 NETWK Unit Status Display
14.8.3 Display example of the NETWK unit status display
(4) Unit error information
Displays the number of unit errors and the error codes.
(5) Link scan time information
Displays the link scan time.
(6) Host station line status
Displays the connection status of the CC-Link IE Field Network communication unit.
No. Item Description
(6) Unit error Displays the number of module errors.
(7) ErrCode Error histories of 16 errors are displayed in 16 lows from the latest.
No. Item Description
(8)
Current LS time Displays the current link scan time.
Max. LS time Displays the maximum link scan time.
Min. LS time Displays the minimum link scan time.
Constant LS time Displays the link scan time set in the parameter.
No. Item Description
(9)
Connection
Displays the connection status of the host station.
Normal (PORT1: communicating, PORT2: communicating)
Normal (PORT1: communicating, PORT2: cable disconnected)
Normal (PORT1: in loopBK communication, PORT2 cable disconnected)
Normal (PORT1: cable disconnected, PORT2: communicating)
Normal (PORT1: cable disconnected, PORT2: in loopBK communication)
Disconnect (PORT1: cable disconnected, PORT2: cable disconnected)
Disconnect (PORT1: cable disconnected, PORT2: connecting a line)
Disconnect (PORT1: connecting a line, PORT2: cable disconnected)
Disconnect (PORT1: connecting a line, PORT2: connecting a line)
PORT1: cable disconnct count 0: No error, 1 or more: Number of accumulated errors
PORT1: line err count 0: No error, 1 or more: Number of accumulated errors
PORT2: cable disconnct count 0: No error, 1 or more: Number of accumulated errors
PORT2: line err count 0: No error, 1 or more: Number of accumulated errors