20.3 ERROR MESSAGE AND SYSTEM ALARM
20.3.2 List of Error Message/System Alarm
20.3.2 List of Error Message/System Alarm
The system alarm detected with GOT is shown below.
Error
code
Error message Action
Channel
No.
storage
303
Set monitor points too
large. Decrease setting
points.
Decrease the number of objects from the displayed screen.
For the number of maximum objects for 1 screen, refer to the
following.
• GT Designer3 Version1 Screen Design Manual
(Fundamentals)
• GT Designer2 Version Screen Design Manual
304
Set trigger points too
large. Decrease setting
points.
The number of objects using Sampling/Cycle during ON/
Cycle during OFF exceeds 100.
Decrease the number of objects.
306
No project data.
Download screen data.
The project data is not downloaded or the screen data is not
sufficient.
Download the project data or screen data.
307 Monitor device not set
The monitor device of the object is not set.
Set the monitor device of the object.
308
No comment data.
Download comment.
The comment file does not exist.
Create the comment file and download to GOT.
309
Device reading error.
Correct device.
The error occurred when reading a continuous device.
Correct the device.
310
Project data does not
exist or out of range.
1. Specified base screen / window screen does not exist in
the project data.
2. Specified base screen / window screen is out of the
permissible area. Specify the existing base screen /
window screen.
311
No. of alarm has
exceeded upper limit.
Delete restored alarm.
The number of alarm histories that can be observed by the
alarm history display function has exceeded the maximum
points.
Delete the restored history to decrease the number of alarm
histories.
312
No. of sampling has
exceeded upper limit.
Delete collected data.
The collection frequency exceeded the upper limit when
"Store Memory" and "Accumulate/Average" were set in the
scatter graph.
1. Approve "Clear trigger" setup in the scatter graph.
2. Set the "Operation at frequency over time" to "Initialize
and Continue" in scatter graph.
315
Device writing error.
Correct device.
Error occurred while writing in the device.
Correct the device.
316
Cannot display or input
operation value. Review
expression.
In indirect specification of comment/parts number, the data
operation result exceeded the range in which device type can
be expressed.
Review the data operational expression, in order not
exceeding the range in which the device type can be
expressed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi GOT1000 GT15 and is the answer not in the manual?

Mitsubishi GOT1000 GT15 Specifications

General IconGeneral
Display Size10.4 inches
Display TypeTFT Color LCD
Resolution640 x 480 pixels
Touch Panel TypeAnalog resistive film
Power Supply24V DC
BacklightLED
Protection RatingIP65 (front panel)
InterfaceRS-232, RS-422/485, USB
Operating Temperature0°C to 50°C
Memory9 MB
Storage Temperature-20 to 60°C
Display Colors256 colors