20.3 ERROR MESSAGE AND SYSTEM ALARM
20.3.2 List of Error Message/System Alarm
20 - 29
17
ADDITION TIMES RESET
FOR MAINTENANCE TIME
NOTIFICATION
18
INSTALLATION OF
COREOS, BOOTOS AND
STANDARD MONITOR OS
19
MAINTENANCE AND
INSPECTION
20
TROUBLESHOOTING
APPENDICESINDEX
505
Warning! Built-in Flash
ROM needs replacement
soon.
The dedicated GS is notifying that the built-in flash memory
writing times have reached 80% or more of the set times.
The GOT must be replaced. In that case, Data backup and re-
setting are needed. The GOT can also be restored by turning
off the notification signal manually. In such a case, turn it OFF
after setting a value greater than the addition times.
506
Warning! Backlight needs
replacement.
The dedicated GS is notifying that the backlight power on
addition time has reached the set time or more.
The GOT can be restored by executing the addition times
reset function after replacing the backlight. The GOT can also
be restored by turning off the notification signal manually. In
such a case, turn it OFF after setting a value greater than the
addition time.
507
Warning! Display section
needs replacement.
The dedicated GS is notifying that the display section power
on addition time has reached the set time or more.
The GOT can be restored by executing the addition times
reset function after replacing the display section. The GOT
can also be restored by turning off the notification signal
manually. In such a case, turn it OFF after setting a value
greater than the addition time.
508
Warning! Touch panel
needs replacement.
The dedicated GS is notifying that the touching count of the
touch key has reached the set count number or more.
The GOT can be restored by executing the addition times
reset function after replacing the touch key. The GOT can also
be restored by turning off the notification signal manually. In
such a case, turn it OFF after setting a value greater than the
addition times.
509
Warning! Built-in Flash
ROM needs replacement.
Change the GOT.
The dedicated GS is notifying that the built-in flash memory
writing times have reached the set times or more.
The GOT must be replaced. In that case, Data backup and re-
setting are needed. The GOT can also be restored by turning
off the notification signal manually. In such a case, turn it OFF
after setting a value greater than the addition times.
510
Clock data input out of
range
The value that is input as clock data is out of the input
enabled range.
In this case, the input value is not accepted.
Confirm the input range of the value to be input as clock data,
and input the proper value again.
511
A blown backlight is
detected.
The backlight is shut off or the lighting status of the backlight
is unstable.
If the error is detected repeatedly, contact your local
Mitsubishi representative.