8 Fault elimination
154 TAPCON® 230 basic 2117246/02 EN © Maschinenfabrik Reinhausen 2012
Characteristics/detail Cause Remedy
Blocking
LED V< illuminated
Undervoltage blocking acti-
ve
Check parameter.
Correct if necessary.
Blocking
LED V> illuminated
Overvoltage blocking active. Check parameter.
Correct if necessary.
Blocking
LED I> illuminated
Overcurrent blocking active. Check parameter.
Correct if necessary.
Bandwidth set too high -
Determine recommended
bandwidth (page 86).
Table 48 Troubleshooting: No control in AUTO mode
8.1.2 Man Machine Interface
Characteristics/detail Cause Remedy
Keys
Does not switch be-
tween MANUAL/AUTO
REMOTE selected. Select LOCAL mode.
Keys
MANUAL and AUTO
LEDs do not light up.
Parameter error.
Reset to factory settings (page
147).
Display
No display.
Contrast incorrectly set.
Set contrast using resistor con-
tact series in front panel.
Voltage supply interrupted. Check voltage supply.
Fuse faulty. Replace fuse.