8 Fault elimination
© Maschinenfabrik Reinhausen 2012 2117246/02 EN TAPCON® 230 basic 157
8.1.4 Customized GPIs/GPOs
Characteristics/detail Cause Remedy
Function expected from
factory setting does not
take place.
Parameterization has been
overwritten manually or via
TAPCON®-trol.
Check active parameters.
Signal discontinuous. Intermittent DC voltage.
Check source of DC voltage.
Check signal transmitter.
Check wiring.
No signal
Info screens <04>,
<05> displaying 0.
Supply voltage too low.
Reset parameter to factory
settings (page 147).
Table 51 Fault elimination: GPIs and GPOs
8.1.5 General faults
Characteristics/detail Cause Remedy
No function
Supply voltage.
Fuse tripped. Check all fuses.
Replace if necessary.
Relays chatter Supply voltage too low. Check supply voltage.
Table 52 Troubleshooting: General faults