7 Functions and settings
148 TAPCON® 230 basic 2117246/02 EN © Maschinenfabrik Reinhausen 2012
7.5.8 Displaying memory overview
The memory overview can be used to display various database entries with
the relevant number of data records. The information is not relevant for opera-
tion. It is only needed for service checks. The following information can be
displayed:
Parameter file
Event data bits
Flash file
Events
To display the database entries, proceed as follows:
1. > Info > 7x .
<14> Memory overview.
2. Press
or to to select an entry.
The relevant number of records is dis-
played.
7.5.9 Displaying event overview
The event overview can be used to display the number of current red and yel-
low events.
The events are marked in color depending on their priority:
Yellow Corresponds to an advance warning or status information.
Red Automatic regulation can block.
Table 46 Color coding of events
The following yellow events may occur:
Motor protective switch tripped
Undercurrent
Function monitoring
Motor runtime exceeded