7 Functions and settings
76 TAPCON® 230 basic 2117246/02 EN © Maschinenfabrik Reinhausen 2012
1. > Normset > 1x .
<01> Desired value 1.
2. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
3. Press
to increase the value or to
reduce it.
4. Press
.
Desired value 1 is set.
7.2.2 Setting the primary voltage
In general, the regulator only indicates the secondary voltage in V if you have
not set the primary voltage. The primary voltage is only displayed if parameter
"Display kV / V" has been set to kV.
Example:
Primary voltage Secondary voltage kV or V Display
No parameterization 100 V V 100 V
110 kV 100 V kV 110 kV
Table 9 Example of displayed values in V or kV
Setting range Step size Factory setting
0 kV...9999 kV
0 kV...999.9 kV
0 kV...99.99 kV
1 kV
0.1 kV
0.01 kV
0 kV
Table 10 Setting range for primary voltage in kV