7 Functions and settings
© Maschinenfabrik Reinhausen 2012 2117246/02 EN TAPCON® 230 basic 89
Setting range Step size Factory setting
0 s to 600 s 1 s 40 s
Table 19 Setting range for delay time T1
To set the delay time T1, proceed as follows:
1. > Control Parameters > Vol-
tage Regulation > 5x
.
<05> Delay Time T1.
2. Press
to highlight a digit.
The digit position you want is highlighted
and the value can be changed.
3. Press
to increase the time or to re-
duce it.
4. Press
.
The delay time is set.