7 Functions and settings
Maschinenfabrik Reinhausen 2014 1013550953/00 EN TAPCON® 230 pro
To set the blocking limit for the maximum permitted circulating reactive cur-
rent, proceed as follows:
1. > Configuration > Parallel operation > Press until the de-
sired parameter is displayed.
ð Circulating reactive current blocking.
2. Press to increase the value or to reduce it.
3. Press .
ð The blocking limit for the maximum permitted circulating reactive current
is set.
Setting tap synchronization
With the tap synchronization method, you need to designate one voltage
regulator as the master and all others as followers. The master handles volt-
age regulation and transmits its current tap positions to all followers via the
CAN bus. The followers compare the tap position received with their own tap
position. If the set permissible tap difference between the tap position re-
ceived and their own position is exceeded, the followers switch to the tap po-
sition received from the master. This ensures that the transformers operating
in parallel are always in the same tap position.
For the tap synchronization method, you can select the following options:
Option Description
Master The voltage regulator is designated as the master.
Follower The voltage regulator is designated as the follower.
Sync.auto Automatic assignment of master or follower.
If no master is detected, the voltage regulator with the
lowest CAN bus address is automatically designated
as the master. All other voltage regulators are desig-
nated as followers.
Table 19: Tap synchronization method
In order to use the sync.auto option, an individual CAN bus address must
be assigned to each voltage regulator. Up to 16 CAN participants are sup-
ported.
To set the tap synchronization method, proceed as follows:
1. > Configuration > Parallel operation > Press until the
desired parameter is displayed.
ð Parallel operation method.
2. Press or until the desired parameter is displayed.
3. Press .
ð The tap synchronization method is set.