10 Messages
Maschinenfabrik Reinhausen 2014144 2374092/04 ENTAPCON® 260
Messages
This chapter contains an overview of the device's messages.
Signal inputs
Input Inscription Function
UC1/2/3-
X1:12
MOTOR-DRIVE
UNIT IN OPERA-
TION
Motor-drive unit is in operation
UC1/2/3-
X1:11
MOTOR PROTEC-
TIVE SWITCH OFF
Motor protective switch has trig-
gered
IO-X1:31
IO-X1:33
See connection dia-
gram
-
IO-X1:12 AUTO Activate AUTO mode
IO-X1:11 MANUAL Activate MANUAL mode
IO-X1:13 RAISE Raise tap position
IO-X1:14 LOWER Lower tap position
UC1/2/3-
X1:14...17,
UC1/2/3-
X1:30...33
BCD1...BCD10 BCD tap input signal
IO-X1:29 PARALLEL GROUP
1, or: See connec-
tion diagram
Assign parallel operation group 1
IO-X1:28 PARALLEL GROUP
2, or: See connec-
tion diagram
Assign parallel operation group 2
IO-X1:16/17 See connection dia-
gram
-
Table 50: Signal inputs
Signal outputs
Relay Inscription Cause
IO-X1:23 See connection
diagram
-
IO-X1:25 See connection
diagram
-
IO-X1:21 FUNCTION
MONITORING
Signal for Function monitoring mes-
sage
IO-X1:10 AUTO Signal if auto mode is active
IO-X1:09 MANUAL Signal if manual mode is active
IO-X1:04 - -
IO-X1:06 TAP DIFFER-
ENCE
Signal if tap position difference of ED1,
ED2, ED3 is greater than or equal to 1
10
10.1
10.2