6 Functions and settings
Maschinenfabrik Reinhausen 2014106 2374092/04 ENTAPCON® 260
To set the average value interval, proceed as follows:
1. > Configuration > Continue > Continue > Memo-
ry > Press until the desired parameter is displayed.
ð Average value interval.
2. Press to increase the time or to reduce it.
3. Press .
ð The average value interval is set.
Setting event memory size
You can use this parameter to configure the event memory size. The event
memory stores instances of values exceeding or falling below the preset
threshold values (V> and V<). It stores this information in high resolution.
The maximum number of events depends on the size of the event memory:
Event memory size 256 kB 512 kB 1024 kB 2048 kB
Maximum number of
events
20 40 80 160
Table 28: Event memory size
Event lasting less than 5 minutes
If the event lasts less than 5 minutes, it is recorded in high resolution . The
high-resolution data are first recorded 10 seconds before the event . If
the voltage has returned to the bandwidth , the event is still recorded until
the overrun time of 10 seconds
has passed.
At a low resolution , the entire process is saved.
6.14.4