PREF Name Block Type Range Default ro\rw Notes
27.10 POWER FACTOR MOTOR INDUCTION REAL 0.50 to 0.99 0.86 rw 3
27.11 OVERLOAD MOTOR INDUCTION REAL 1.0 to 5.0 2.0 rw 3
27.14 STATOR RES MOTOR INDUCTION REAL 0.0000 to 250.0000 Ohm 0.2851 Ohm rw 3,5
27.15 LEAKAGE INDUC MOTOR INDUCTION REAL 0.00 to 300.00 mH 9.08 mH rw 3,5
27.16 MUTUAL INDUC MOTOR INDUCTION REAL 0.00 to 3000.00 mH 36.30 mH rw 3,5
27.17 ROTOR TIME CONST MOTOR INDUCTION REAL 10.00 to 30000.00 ms 506.08 ms rw 3,5
27.23 TOTAL INERTIA MOTOR INDUCTION REAL 0.0000 to 300.0000 kgm2 0.0000 kgm2 rw 5
27.24 SUPPLY VOLTAGE MOTOR INDUCTION ENUM 0 : 230V
1 : 380V TO 460V
2 : 500V
3 : 575V
4 : 690V
380V TO 460V rw 3
29.01 DEFLUX TIME INJ BRAKING REAL 0.1 to 20.0 s 1.0 s rw 3,5
29.02 FREQUENCY INJ BRAKING REAL 1.0 to 500.0 Hz 6.0 Hz rw 3,5
29.03 I-LIM LEVEL INJ BRAKING REAL 50.00 to 150.00 % 100.00 % rw
29.04 DC PULSE INJ BRAKING REAL 0.0 to 100.0 s 2.0 s rw 3,5
29.05 FINAL DC PULSE INJ BRAKING REAL 0.0 to 10.0 s 3.0 s rw 3,5
29.06 DC LEVEL INJ BRAKING REAL 0.00 to 25.00 % 1.25 % rw 3,5
29.07 TIMEOUT INJ BRAKING REAL 0.0 to 600.0 s 90.0 s rw
29.08 BASE VOLTS INJ BRAKING REAL 0.00 to 115.47 % 75.00 % rw 3,5
29.09 ACTIVE INJ BRAKING BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
30.01 ENABLED KEYS OP STATION WORD 0000 to FFFF 00F0 rw
30.02 OP VERSION OP STATION WORD 0000 to FFFF 0000 ro Output
30.03 OP DATABASE OP STATION BOOL 0 : FALSE
1 : TRUE
FALSE ro Output