Programming
Page
D-192
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
PREF Name Block Type Range Default ro\rw Notes
21.28 USER FREQ 10 FLUXING REAL 0.0 to 100.0 % 100.0 % rw
21.29 USER VOLTAGE 10 FLUXING REAL 0.0 to 100.0 % 100.0 % rw
22.01 ENABLE SLEW RATE LIMIT BOOL 0 : FALSE
1 : TRUE
TRUE rw
22.02 ACCEL LIMIT SLEW RATE LIMIT REAL 1.0 to 1200.0 Hz/s 500.0 Hz/s rw
22.03 DECEL LIMIT SLEW RATE LIMIT REAL 1.0 to 1200.0 Hz/s 500.0 Hz/s rw
23.01 ENABLE SLIP COMP BOOL 0 : FALSE
1 : TRUE
FALSE rw 2
23.02 MOTORING LIMIT SLIP COMP REAL 0.0 to 600.0 RPM 150.0 RPM rw 5
23.03 REGEN LIMIT SLIP COMP REAL 0.0 to 600.0 RPM 150.0 RPM rw 5
25.01 ENABLE STABILISATION BOOL 0 : FALSE
1 : TRUE
TRUE rw
27.01 CONTROL MODE MOTOR INDUCTION ENUM 0 : VOLTS / Hz
1 : SENSORLESS VEC
2 : CLOSED-LOOP VEC
VOLTS / Hz rw 2
27.02 POWER MOTOR INDUCTION REAL 0.00 to 3000.00 kW 30.00 kW rw 3
27.03 BASE FREQUENCY MOTOR INDUCTION REAL 7.5 to 1000.0 Hz 50.0 Hz rw 2,4
27.04 MOTOR VOLTAGE MOTOR INDUCTION REAL 0.0 to 690.0 V 400.0 V rw 3,4
27.05 MOTOR CURRENT MOTOR INDUCTION REAL 0.00 to 3276.70 A 54.00 A rw 2,3
27.06 MAG CURRENT MOTOR INDUCTION REAL 0.00 to 3276.70 A 16.20 A rw 3
27.07 NAMEPLATE RPM MOTOR INDUCTION REAL 0.0 to 30000.0 RPM 1470.0 RPM rw 3,4
27.08 MOTOR
CONNECTION
MOTOR INDUCTION ENUM 0 : DELTA
1 : STAR
STAR rw 3,4
27.09 MOTOR POLES MOTOR INDUCTION ENUM 0 : 2 POLE
1 : 4 POLE
2 : 6 POLE
3 : 8 POLE
4 : 10 POLE
5 : 12 POLE
4 POLE rw