EasyManua.ls Logo

Parker ac890 - Page 541

Parker ac890
640 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page
D-191
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
PREF Name Block Type Range Default ro\rw Notes
21.01 V/F SHAPE FLUXING ENUM 0 : LINEAR LAW
1 : FAN LAW
2 : USER DEFINED
LINEAR LAW rw
21.02 BASE FREQUENCY FLUXING REAL 7.5 to 500.0 Hz 50.0 Hz rw 1,4
21.03 FIXED BOOST FLUXING REAL 0.00 to 25.00 % 0.00 % rw 3
21.04 AUTO BOOST FLUXING REAL 0.00 to 25.00 % 0.00 % rw
21.08 ACCELRTN BOOST FLUXING REAL 0.00 to 25.00 % 0.00 % rw
21.09 ENERGY SAVING FLUXING BOOL 0 : FALSE
1 : TRUE
FALSE rw
21.10 USER FREQ 1 FLUXING REAL 0.0 to 100.0 % 10.0 % rw
21.11 USER VOLTAGE 1 FLUXING REAL 0.0 to 100.0 % 10.0 % rw
21.12 USER FREQ 2 FLUXING REAL 0.0 to 100.0 % 20.0 % rw
21.13 USER VOLTAGE 2 FLUXING REAL 0.0 to 100.0 % 20.0 % rw
21.14 USER FREQ 3 FLUXING REAL 0.0 to 100.0 % 30.0 % rw
21.15 USER VOLTAGE 3 FLUXING REAL 0.0 to 100.0 % 30.0 % rw
21.16 USER FREQ 4 FLUXING REAL 0.0 to 100.0 % 40.0 % rw
21.17 USER VOLTAGE 4 FLUXING REAL 0.0 to 100.0 % 40.0 % rw
21.18 USER FREQ 5 FLUXING REAL 0.0 to 100.0 % 50.0 % rw
21.19 USER VOLTAGE 5 FLUXING REAL 0.0 to 100.0 % 50.0 % rw
21.20 USER FREQ 6 FLUXING REAL 0.0 to 100.0 % 60.0 % rw
21.21 USER VOLTAGE 6 FLUXING REAL 0.0 to 100.0 % 60.0 % rw
21.22 USER FREQ 7 FLUXING REAL 0.0 to 100.0 % 70.0 % rw
21.23 USER VOLTAGE 7 FLUXING REAL 0.0 to 100.0 % 70.0 % rw
21.24 USER FREQ 8 FLUXING REAL 0.0 to 100.0 % 80.0 % rw
21.25 USER VOLTAGE 8 FLUXING REAL 0.0 to 100.0 % 80.0 % rw
21.26 USER FREQ 9 FLUXING REAL 0.0 to 100.0 % 90.0 % rw
21.27 USER VOLTAGE 9 FLUXING REAL 0.0 to 100.0 % 90.0 % rw