Programming
Page
D-232
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
A
B
C
D
E
1
2
3
4
5
6
7
PREF Name Block Type Range Default ro\rw Notes
121.06 POSIT'N INTEGRAL POSITION LOOP REAL _.xxxx 0.0000 deg ro Output
121.07 ENABLE POSITION LOOP BOOL 0 : FALSE
1 : TRUE
FALSE rw
121.08 SPD FEEDFORWARD POSITION LOOP REAL _.xxxx 0.0000 Hz ro Output
121.09 PID OUTPUT POSITION LOOP REAL _.xxxx 0.0000 Hz ro Output
121.10 OUTPUT POSITION LOOP REAL _.xxxx 0.0000 Hz ro Output
121.11 LIMIT POSITION LOOP REAL 0.00 to 300.00 % 10.00 % rw
121.12 LIMITING POSITION LOOP BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
121.13 FOLLOWING ERROR POSITION LOOP REAL _.xxxx 0.0000 deg ro Output
121.14 TOTAL OFFSET POSITION LOOP REAL _.xxxx 0.0000 ro Output
121.15 POSITION DEMAND POSITION LOOP REAL _.xx 0.00 deg ro Output
121.16 MODE POSITION LOOP ENUM 0 : DISABLED
1 : ENABLED
2 : UNSYNCHRONISED
3 : SYNCHRONISED
4 : ABSOLUTE
DISABLED ro Output
122.01 FRICTION @ 0 RPM INERTIA COMP REAL 0.00 to 100.00 % 0.00 % rw
122.02 FR'N @ NMPLT RPM INERTIA COMP REAL 0.00 to 100.00 % 0.00 % rw
122.03 RELATIVE INERTIA INERTIA COMP REAL 0.0000 to 30000.0000 % 0.0000 % rw
122.04 FRICTION COMP INERTIA COMP REAL _.xx 0.00 % ro Output
122.05 INERTIA COMP INERTIA COMP REAL _.xx 0.00 % ro Output
122.06 TORQ
FEEDFORWARD
INERTIA COMP REAL _.xx 0.00 % ro Output
122.07 SPEED PI OUTPUT INERTIA COMP REAL _.xx 0.00 % ro Output
123.01 INHIBIT OVER SPEED TRIP BOOL 0 : FALSE
1 : TRUE
FALSE rw
123.02 THRESHOLD OVER SPEED TRIP REAL 0.00 to 300.00 % 150.00 % rw

Table of Contents