For your safety
8482_en_03 PHOENIX CONTACT 11
1.4 Notes on using the AXC 1050 XC controller in
potentially explosive areas of zone 2
Installation notes
1. The controller is a device of category 3 and is suitable for installation in potentially ex-
plosive areas of zone 2.
The controller meets the requirements of EN 60079-0:2012+A11:2013 and
EN 60079-15:2010.
2. The controller must be installed, started up, operated, and maintained by qualified spe-
cialist personnel only.
3. Follow the installation instructions described in this user manual, in the device-specific
packing slip, and in the UM EN AXL F SYS INST user manual.
4. When installing and operating the device, the applicable safety directives (including na-
tional safety directives), accident prevention regulations, as well as general technical
regulations must be observed.
5. For the safety data, please refer to the corresponding documentation (user manual,
packing slip) and the certificates (declaration of conformity and other approvals, if ap-
plicable).
6. Access to the circuits inside the controller is not permitted. Do not repair the controller
yourself but replace it with an approved controller of the same type.
Repairs may only be performed by the manufacturer. The manufacturer is not liable for
damage resulting from noncompliance.
7. The IP20 degree of protection (EN 60529) requires that the device be used in a clean
and dry environment.
8. Do not subject the controller to mechanical strain and/or thermal loads that exceed the
limits specified in the product documentation.
9. The controller is not designed for use in potentially dust-explosive atmospheres. If dust
is present, install the device in suitable, approved housing. Please note the surface
temperature of the housing.
10. Stop the device and immediately remove it from the potentially explosive area if it is
damaged or was subject to an impermissible load or stored incorrectly or if it malfunc-
tions.
Approval in accordance with the 2014/34/EU directive
II 3 G Ex nA IIC T4 Gc X
WARNING: Explosion hazard
Please make sure that the following notes and instructions are observed!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact AXC 1050 and is the answer not in the manual?

Phoenix Contact AXC 1050 Specifications

General IconGeneral
BrandPhoenix Contact
ModelAXC 1050
CategoryController
LanguageEnglish

Related product manuals