HUNTER-PRO 32 Intruder Alarm System - Installation Manual
44
3.17
Connecting Mains
IMPORTANT!
Verify that the power cord is disconnected from the mains power
supply.
Connect the three power cord wires to the connection terminals of the Power
Supply terminals. Verify that the transformer outputs are connected to the AC
terminals on the PCB, and that the transformer supplies 2A.
With an Ohm meter, check for continuity between the grounding point on the
control panel, PCB and GND terminal, to the electrical outlet grounding point.
The resistance must be less than 1 Ohm.
Now you can connect the power cord to the mains power source
(230VAC).
NOTE:
A current limit device, such as a circuit breaker, fuse, etc., must be
connected in series to the power cord.
You must connect the
Electrical grounding!
Connect AC mains power supply.
Connect the backup battery to the fast connection terminals, red wire
to (+) and black wire to (-).
IMPORTANT!
Failing to connect the cables as described will permanently damage
the control panel!
NOTE:
If you connect the battery before the Mains (AC), an AC FAULT will be
displayed until you connect the AC. The AC FAULT will be logged in
memory.
3.18
Initializing the System
Make sure the connections to the system are in order as described in
previous sections.