HUNTER-PRO 32 Intruder Alarm System - Installation Manual
90
Check the following:
The telephone line is properly connected to the IN terminal block.
In Communication menu the “P” for telephone is programmed with +.
The system is programmed to pick up after a reasonable number of rings – not
more than 10.
7.3.9 Automatic Arming Failure
Check the following:
No Clock failure indication.
The Automatic arming feature is activated – The letter
A
is displayed to the left
of the clock.
Clock is set to the correct time.
7.3.10 Open Zone does not cause Alarm
Check the following:
The Zone is not temporarily or permanently bypassed,
The zone is programmed for the correct response, siren, relay, etc.
If the zone is assigned to more than one partition, then all the
partitions it is assigned to must be armed.
Detectors are correctly installed and are not malfunctioning.
Zone sensitivity settings.
Cross zoning settings.
Pulse counter settings.
Power supply is not low – AC and backup battery power levels.