Because RFL and Hubbell® have a policy of continuous product improvement, we reserve the right to change designs and specications without notice.
RFL VF-6I RFL Electronics Inc.
November 17, 2004 8 (973) 334-3100
4. Insert the desired Module Adapter into the rear of the slot which will hold the RFL VF-6I
module, and make all connections to the module Adapter.
If an MA-301 or MA-324 Module Adapter is being used, plug the 50-pin Telco
connector into its 50-pin connector.
If an MA-301A-1 Module Adapter is being used, connect all signal wiring to the
terminal strip at the rear of the MA-301A-1 using Figure 3 as a guide.
If an MA-301B-1 Module Adapter is being used, connect all signal wiring to the
terminal strip at the rear of the MA-301B-1 using Figure 4 as a guide.
5. Refer to Figure 6 and Table 1 for the location of DIP switches on the VF-6I.
6. Set DIP switches SW1-1 through SW1-6 to the desired remote address (SCB address).
For remote access, each channel module in the IMUX 2000 must have a
distinct module address. Valid addresses are the numbers “1” to “36”. In most
installations, the address will be set to the slot number in the shelf the module is
occupying. Table 2 shows the switch settings for the module address.
7. Set DIP switches SW2-1 through SW2-5 to select the desired time slot.
SW2-1 through SW2-5 select the time slot assignment, using the binary codes
shown in Table 3 of this Instruction Data Sheet.
8. Set DIP switch SW2-6 to enable or disable bus A.
Place SW2-6 in the DOWN position to transmit on bus A and receive on bus B.
Place SW2-6 in the UP position to disable bus A.