Message
Test mode active
The computer is in test mode for maintenance purposes.
Module type not correct
The type of module found does not match the type of module that was expected.
The module has overloaded.
The electric current protection of the outputs has been activated.
Reset the module. Max. current for each output is 500 mA, max. current for
each module side is 2 A.
UV lamps out of operation
One or more UV lamps have been switched off manually. To ensure effective
disinfection, all UV lamps must be in operation.
Watchdog switched off, remove watchdog jumper
Alarm monitoring of the process computer in question is not functioning.
Contact your installer.
Your installer can remove the watchdog jumper for you, so alarm monitoring
will function again.
Acid tank empty (disinfection)
The following error has occurred during disinfection:
The system has detected that the acid tank is empty.
Refill the acid tank.
Acid tank empty (cleaning quartz tubes)
The following error has occurred while the quartz tubes were being cleaned:
The system has detected that the acid tank is empty.
Refill the acid tank.
VitaLite
102