<M> Settings / Unit / Characteristics
Max. total flow [m3/h]
Here you enter the flow rate at which the flow sensor
will generate a 20mA signal.
K-factor drain flow [p/l]
Here you enter the K-factor in pulses/litre as specified
by the manufacturer of the flow sensor. This factor
depends on the diameter of the tube in which the
sensor has been installed.
See K-factor table at
the start of this
section.
Max. drain flow [m3/h]
Here you enter the flow rate at which the flow sensor
will generate a 20mA signal.
Delay system pump on [hh:mm:ss]
This sets the number of seconds that system pump
activation will be delayed to allow the valves open
first.
Maximum time UV lamp on [hh:mm:ss]
This sets the maximum time that the UV lamps will
remain switched on if disinfection is interrupted to
clean the quartz tubes or flush the filter. This setting
allows you to reduce the frequency with which the
lamps are switched on and off, increasing the lifespan
of the lamps.
00:00:00, otherwise
the unit will warm
up too quickly
during filter flushing
or cleaning of the
quartz tubes.
Time between switching lamps on [hh:mm:ss]
This sets the delay time between the activation of the
lamps.
The purpose of this delay time is to prevent a high
inrush current.
Disable pH sensor alarm
l Yes: Detection of pH sensor alarm is disabled.
l No: Detection of pH sensor alarm is enabled.
Water temperature [°C]
Here you enter the assumed water temperature. This
is used to calculate the viscosity of the water.
Only applicable if EC
sensor is present.
Node ID ctrl. radiation sensor
Here you enter the node ID of this Modbus sensor.