Operating Instructions Chapter 11
Flexi Classic Gateways
8011834/YT28/2016-03-15 © SICK AG • Industrial Safety Systems • Germany • All rights reserved
147
Subject to change without notice
Technical specifications
11 Technical specifications
11.1 Technical specifications fieldbus
11.1.1 PROFIBUS
Interface Min. Typ. Max.
Fieldbus PROFIBUS-DP-V0
Interface level RS-485
Connector technology D-Sub socket 9-pin
Slave address 0 99
Baud rate (adjustment
automatic)
12 MBaud
Baud rate (kBits/s with
standard cable)
Max. cable length
9.6 / 19.2 / 93.75 1200 m
187.5 1000 m
500 400 m
1500 200 m
12000 100 m
Cable parameters see chapter 4 “PROFIBUS DP Gateway” from p. 27.
11.1.2 CANopen
Interface Min. Typ. Max.
Fieldbus CANopen
Interface level
ISO DIS 11898
Connector technology
Open style connector,
5-pin removable terminal
Slave address
Address range 1..99,
Setting via rotary switch
Baud rate
125, 250, 500, 800, 1000 Kbit/s,
Setting via DIP switch
Function Gateway
Function indication 3 LEDs green/red
Controls
2 switches 10-position
1 DIP switch, 4-pole
Terminals Removable screw terminals
Max. number of modules
/ status in the system
1 / interaction-free slave on the internal
safety bus, slave on the fieldbus
Cable parameters see chapter 5 “CANopen Gateway” from p. 32.
Tab.
121
:
Technical
specifications