2.5.5.5 I/O Assignment
The assignment of the HW pins to the data points is done according to the following scheme.
2.5.5.5.1 Inputs
HW pin Data point
Measured values on AI-2300 (±20 mA), AI-2302 (±6 mA), AI-2303 (±24 mA)
IN V00+ / IN V00-
IN V01+ / IN V01-
:
IN V15+ / IN V15-
Measured value V00
Measured value V01
:
Measured value V15
Optional measured values via SM-0570 (±20 mA)
[IOMx] I/O 0 / [IOMx] I/O 1
[IOMx] I/O 4 / [IOMx] I/O 5
Measured value [IOMx] I/O 0-1
Measured value [IOMx] I/O 4-5
Optional measured values via SM-0570 (Pt100, Ni100)
[IOMx] I/O 0 / [IOMx] I/O 1 /
[IOMx] I/O 2 / [IOMx] I/O 3
[IOMx] I/O 4 / [IOMx] I/O 5 /
[IOMx] I/O 6 / [IOMx] I/O 7
Measured value [IOMx] I/O 0-3
Measured value [IOMx] I/O 4-7
Optional integrated totals via SM-0574 (5 kHz, 24…60 VDC)
[IOMx] I/O 0 / [IOMx] I/O 1
[IOMx] I/O 4 / [IOMx] I/O 5
Measured value [IOMx] I/O 0-1
Measured value [IOMx] I/O 4-5
(x = 0…3)
2.5.5.5.2 Outputs
HW Pin Data Point
Optional setpoint values via SM-0572 (±20 mA, ±10 mA, ±5 mA; ±1 V, ±10 V)
[IOMx] I/O 2 / [IOMx] I/O 3
[IOMx] I/O 6 / [IOMx] I/O 7
Measured value [IOMx] I/O 2-3
Measured value [IOMx] I/O 6-7
(x = 0…3)
Note
In the SICAM TOOLBOX II, always AI-2300/PASI25 has to be equipped. The following parameters must
be set correspondingly:
AI-2300 AI-2302 AI-2303
Default-load: yes no no
Bipolar acquisition: X_100%: 20 mA X_100%: 6 mA X_100%: 24 mA
X_0%: 20 mA X_0%: -6 mA X_0%: -24 mA
Unipolar acquisition: X_100%: 20 mA X_100%: 6 mA X_100%: 24 mA
X_0%: 0 X_0%: 0 X_0%: 0