Automation Units and Automation Networks
SICAM RTUs, SICAM AK 3 User Manual 237
DC2-028-2.03, Edition 07.2016
6.1.1.2 SICAM AK 3 - SICAM AK 3 PE, electrically connected
Basic unit SICAM AK 3 to peripheral elements in SICAM AK 3 expansion board rack; electri-
cally connected
• To one basic system element CP-2016/CPCX26 or CP-2019/PCCX26 one bus line with
max. 16 peripheral elements can be connected.
• Depending on the slot of the basic system element the socket connector for the electrical
Ax 1703 peripheral bus has to be selected.
(Examples: Slot 0 ð socket connector X2/M-Ax
Slot 1 ð socket connector X4/C1-Ax)
Necessary modules and cables
Designation Item-Number/MLFB
Basic unit
SICAM AK 3
CP-2016
Master control element CP-2016/CPCX26
BC2-016 / 6MF10130CA160AA0
CP-2019
Processing and communication element CP-
2019/PCCX26
BC2-019 / 6MF10132CA100AA0
Cable • Patch cable CAT5 (4x2) AWG26/7 T41-255 (1m) / 6MF13040BC550AA0
T41-251 (2m) / 6MF13040BC510AA0
T41-252 (3m) / 6MF13040BC520AA0
Peripheral elements
SICAM AK 3
CM-2843
SICAM AK 3 expansion board rack
GC2-843 / 6MF11130CJ430AA0
PS-263x DI-2110
DO-2210 AI-2300 A I-2301
DI-2110
DI-2110
DI-2110
AI-2301
SICAM AK
PS-263x
SICAM AK
CP-2016 DI-2110DO-2210 AI-2300C P-2019
AI-2301
DI-2110 DI-2110 DO-2210 AI-2300CP-2019
AI-2301AI-2301
DI-2110DI-2110 DI-2110
CP-2016
CP-2019
max. 16 peripheral elements
(electrical)
16 Mbps
patch-cable, length up to 3 m
SICAM AK 3
base unit