1.8.4 PIN Assignment Peripheral Cable
PIN
Farbe
colour
DI-2110/11
Signal
DO-2201
Signal
DO-2210
Signal
AI-2300
Signal
AI-2300
Signal
SM-0570
Signal
SM-0571
Signal
SM-0572
Signal
SM-0574
AI-2301
Signal
CP-2016
Signal
1 wsbl/bl whbu/bu a1 IN D00 a1 OUT D00+ a1 CA00 a1 IN V00+ a1 IN V00+ a1
2 bl/wsbl bu/whbu b1 IN D01 b1 OUT D00- b1 CA01 b1 IN V00- b1 IN V00- b1
3 wsbl/ge whbu/ye c1 IN D02 c1 OUT D01+ c1 CA02 c1 IN V01+ c1 IN V01+ c1
4 ge/wsbl ye/whbu a2 IN D03 a2 OUT D01- a2 CA03 a2 IN V01- a2 IN V01- a2 SYNC1
5 wsbl/gn whbu/gn b2 IN D04 b2 OUT D02+ b2 CA04 b2 no con. b2 IN IREF00+ b2
6 gn/wsbl gn/whbu c2 IN D05 c2 OUT D02- c2 CA05 c2 no con. c2 IN IREF00- c2 SYNC2
7 wsbl/br whbu/bn a3 IN D06 a3 OUT D03+ a3 CA06 a3 IN V02+ a3 IN V02+ a3
8 br/wsbl bn/whbu b3 IN D07 b3 OUT D03- b3 CA07 b3 IN V02- b3 IN V02- b3
9 wsbl/sw whbu/bk c3 IN PM0 c3 OUT D04+ c3 COMA c3 IN V03+ c3 IN V03+ c3
10 sw/wsbl bk/whbu a4 COM0 a4 OUT D04- a4 GRA a4 IN V03- a4 IN V03- a4 SYNC_GND
11 wsge/bl whye/bu b4 no con. b4 no con. b4 no con. b4 no con. b4 IN IREF01+ b4
12 bl/wsge bu/whye c4 no con. c4 no con. c4 no con. c4 no con. c4 IN IREF01- c4 SYNC_GND
13 wsge/ge whye/ye a5 IN D08 a5 OUT D05+ a5 CB00 a5 IOM0 I/O 0 IN V0+ IN IREF0- no con. IN IC0+ a5 IN V04+ a5
14 ge/wsge ye/whye b5 IN D09 b5 OUT D05- b5 CB01 b5 IOM0 I/O 1 IN V0- IN IREF0+ no con. IN IC0- b5 IN V04- b5
15 wsge/gn whye/gn c5 IN D10 c5 OUT D06+ c5 CB02 c5 IOM0 I/O 2 no con. IN V0- OUT V0+ no con. c5 IN V05+ c5
16 gn/wsge gn/whye a6 IN D11 a6 OUT D06- a6 CB03 a6 IOM0 I/O 3 no con. IN V0+ OUT V0- no con. a6 IN V05- a6
17 wsge/br whye/bn b6 IN D12 b6 OUT D07+ b6 CB04 b6 no con. b6 IN IREF02+ b6
18 br/wsge bn/whye c6 IN D13 c6 OUT D07- c6 CB05 c6 no con. c6 IN IREF02- c6
19 wsge/sw whye/bk a7 IN D14 a7 OUT D08+ a7 CB06 a7 IOM0 I/O 4 IN V1+ IN V1- no con. IN IC1+ a7 IN V06+ a7
20 sw/wsge bk/whye b7 IN D15 b7 OUT D08- b7 CB07 b7 IOM0 I/O 5 IN V1- IN V1+ no con. IN IC1- b7 IN V06- b7
21 wsgn/bl whgn/bu c7 IN PM1 c7 OUT D09+ c7 COMB c7 IOM0 I/O 6 no con. IN IREF1- OUT V1+ no con. c7 IN V07+ c7
22 bl/wsgn bu/whgn a8 COM1 a8 OUT D09- a8 GRB a8 IOM0 I/O 7 no con. IN IREF1+ OUT V1- no con. a8 IN V07- a8
23 wsgn/ge whgn/ye b8 no con. b8 no con. b8 no con. b8 no con. b8 IN IREF03+ b8

Table of Contents