EasyManua.ls Logo

Siemens SIDOOR ATD4 W Series - Page 192

Siemens SIDOOR ATD4 W Series
352 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter ID Adjustment range Factory set‐
ting
Unit Description
p100 0 = FBLOCK + Bus
1 = FBLOCK + relay
0 Default command mode:
For the ATD420W, ATD430W control units the com‐
mand input via the bus system is activated in the de‐
fault setting -> parameter p100 = 0. This means that
the FBLOCK drive orders can only be executed in the
drive state "S4: Z_MODE" (see Figure 4-4 State graph
control unit (Page 163)).
For the ATD401W control unit with relay module, no
command mode is possible via the bus system. For
this control unit variant, parameter p100 = 1 must
always be set. Otherwise, the control unit cannot be
controlled via the digital inputs.
r200 1 … 65535
0 = Checksum invalid
Checksum for the default parameters (see Checksum
parameters (as of V1.12) (Page 77))
r201 1 … 65535
0 = Checksum invalid
Checksum for the learn run parameters (see Check‐
sum parameters (as of V1.12) (Page 77))
r202 0 … 65535 Change counter for the default parameters
(see Checksum parameters (as of V1.12) (Page 77))
r203 0 … 65535 Firmware version
The version is output as "MajorVer*100 + MinorVer".
e. g. 󹪝rmware version "1.13.1234" is output as "113".
r204 0 = Checksum invalid
1 = Checksum valid
Validity of the checksum for the default parameters
r200, r201.
p2080 0 … 65535 FFFF (hex) DCMD masking 󹪝eldbus
Each bit in the mask 󹪝lters the corresponding bit in
TSW1:
0: CMD bit is not allowed to pass
1: CMD bit is allowed to pass
p2081 0 … 65535 FFFF (hex) DCMD masking FBLOCK
Each bit in the mask 󹪝lters the corresponding bit in
TSW1:
0: CMD bit is not allowed to pass
1: CMD bit is allowed to pass
Controllers
5.9 Operation and con󹪝guration of the control unit
ATD4xxW for industrial applications
190 System Manual, 06/2022, A5E51901827B AA

Table of Contents

Related product manuals