Parameterizing the Mobile Panel   
5.8 General settings 
  Mobile Panels 2nd Generation 
112  Operating Instructions, 09/2018, A5E33876626-AC 
Requirement  
The Control Panel is open. 
Procedure 
1.  Open the "Transfer Settings" dialog using the "Transfer" icon. 
2.  Change to the "Directories" tab. 
 
Storage location for project file, cannot be set 
Directory where the compressed source file of your project is saved 
Storage location and initialization file for process operation, cannot be set 
Delay time for project start 
3.  Select a memory location from the "Project Backup" text box. 
The storage location can be a storage medium or the local network. During the next 
backup process, the project's source file is stored in the specified location. 
4.  Select the desired delay time for project start from the "Wait [sec]" selection box. 
The delay time sets how long the Start Center is displayed before the project starts. 
Permissible values are 1, 3, 5 and 10 seconds, for HMI device image versions ≥V14 SP1 
additionally: 60 seconds. 
You can also select: 
– 
0 seconds 
The project starts immediately. The Start Center is 
not displayed. 
–  Forever 
The project does not start. The Start Center is displayed permanently. 
 
Note 
For the Start Center to be accessed after the project starts, an operating element must be 
configured in the project with the "C
lose project" function. 
5.  Confirm your entries with "OK". 
The dialog closes. 
The storage location and delay time for the HMI device are now set.