Fail-safe operation
9.1 Connecting the connecting cable
Mobile Panels 2nd Generation
210 Operating Instructions, 09/2018, A5E33876626-AC
Connection to a connection box with the assigned operating mode "Stop button evaluated by
safety relay"
Plug the connecting cable into a connection box.
The project starts as configured in the Control Panel. The project start screen appears
after startup.
The stop button is active and does not light up.
Connection to a connection box with the assigned operating mode "E-stop button evaluated
by safety relay"
Plug the connecting cable into a connection box.
The project starts as configured in the Control Panel. The project start screen appears
after startup.
The emergency stop button is active and lights up.
Connection to a connection box with the assigned operating mode "E-stop button evaluated
by PROFIsafe"
Plug the connecting cable into a connection box.
The project starts as configured in the Control Panel.
PROFIsafe communication is established.
The Mobile Panel is logged on automatically in the safety program.
The project start screen appears after startup.
The emergency stop button is active and lights up.
Response to errors
1. If an error occurs after you attach the connecting cable, a corresponding error message is
displayed.
2. Check the connecting cable and the plug-in connection on the connection box. Read the
message text and follow the instructions in the error message
You can find additional information on error scenarios in the following sections:
Safety-related dialogs (Page 212)
Troubleshooting (Page 267)
See also
Connecting the KTP Mobile connecting cable to the connection box (Page 73)
Entering and deleting a password (Page 105)

Table of Contents

Other manuals for Siemens SIMATIC HMI series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI series and is the answer not in the manual?

Siemens SIMATIC HMI series Specifications

General IconGeneral
SeriesSIMATIC HMI
CategoryControl Panel
Display TypeTFT LCD
Touch ScreenYes (resistive or capacitive, depending on model)
ProcessorVaries by model (e.g., ARM-based processors)
StorageVaries by model (e.g., Flash memory, microSD card slot)
Communication InterfacesEthernet, USB
Protection ClassIP65 (front panel), depending on model
Operating Temperature0 to 50°C, -20 to 60°C
Power Supply24 V DC
Memory128 MB, 256 MB