When a control command is received at the respective digital input, the motor rotates at ±150
rpm. The same ramp-up and ramp-down times as described above apply.
5.3.3 V/f control or speed control
For induction motors, there are two di󹪜erent open-loop control or closed-loop control
techniques:
V/f control (calculation of the motor voltage using a characteristic curve)
Closed-loop speed control (also: 󹪝eld-oriented control or vector control)
Criteria for selecting either V/f control or speed control
In many applications, the V/f control su󹪟ces to change the speed of induction motors. Examples
of typical applications for V/f control include:
Pumps
Fans
Compressors
Horizontal conveyors
When compared to V/f control, vector control o󹪜ers the following advantages:
The speed is more stable for motor load changes.
Shorter accelerating times when the setpoint changes.
Acceleration and braking are possible with an adjustable maximum torque.
Improved protection of the motor and the driven machine as a result of the adjustable torque
limiting.
Torque control is only possible with vector control.
Examples of typical applications in which speed control is used:
Hoisting gear and vertical conveyors
Winders
Extruders
It is not permissible to use speed control in the following cases:
If the motor is too small in comparison to the converter (the rated motor power must not be
less than one quarter of the rated converter power)
When you operate several motors on one converter
When the maximum motor speed exceeds the following values:
Commissioning
5.3 Prepare commissioning
Distributed converter for SIMOGEAR geared motors
104 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL