A.3 Electromagnetic Compatibility
The SINAMICS G110M drives have been tested in accordance with the EMC Product Standard
EN 61800-3:2004.
Details see declaration of conformity
Condition
The drive is installed in accordance with the manufacturer’s guidelines and in accordance with
good EMC practices.
Description
Table A-9 Compliance Table
Category C2 - First Environment - Professional Use
Article number Remark
6SL3517-1BE11-*A*0
6SL3517-1BE12-*A*0
6SL3517-1BE13-*A*0
6SL3517-1BE14-*A*0
6SL3517-1BE16-*A*0
6SL3517-1BE17-*A*0
6SL351701BE21-*A*0
Converter with integrated Class A lters.
The converter meets the requirements for category C2 for conducted emis‐
sions.
In a domestic environment this product may cause radio interference in which
case supplementary mitigation measures may be required.
Precondition
Install all drives in accordance with the manufacturer’s guidelines and in accordance with good
EMC practices.
Use screened cable type CY. The maximum cable length is 15 m, at a switching frequency of 4
kHz
Appendix
A.3 Electromagnetic Compatibility
Distributed converter for SIMOGEAR geared motors
412 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL