8.17.2 Invert setpoint
Function description
S
[
\
[
\
W
\\[[
The function inverts the sign of the setpoint using a binary signal.
Example
To invert the setpoint via an external signal, interconnect parameter p1113 with a binary signal
of your choice.
Table 8-54 Application examples showing how a setpoint is inverted
Parameter Description
p1113 = 722.1 Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Converter inverts the setpoint.
p1113 = 2090.11 Inverts the setpoint via the eldbus (control word 1, bit 11).
Parameter
Number Name Factory setting
p1113[C] BI: Setpoint inversion Dependent on the
converter
Advanced commissioning
8.17 Setpoint calculation
Distributed converter for SIMOGEAR geared motors
270 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL