EasyManua.ls Logo

Siemens SINAMICS G110M - Setpoint Calculation; Overview

Siemens SINAMICS G110M
428 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.17 Setpoint calculation
8.17.1 Overview
Overview
Setpoint processing in󹪞uences the setpoint using the following functions:
"Invert" inverts the motor direction of rotation.
The "Inhibit direction of rotation" function prevents the motor from rotating in the incorrect
direction; this function can make sense for conveyor belts, extruders, pumps and fans, for
example.
The "Skip frequency bands" prevent the motor from being continuously operated within
these skip bands. This function avoids mechanical resonance e󹪜ects by only permitting the
motor to operate brie󹪞y at speci󹪝c speeds.
The "Speed limitation" function protects the motor and the driven load against excessively
high speeds.
The "Ramp-function generator" function prevents the setpoint from suddenly changing. As
a consequence, the motor accelerates and brakes with a reduced torque.
,QKLELW
GLUHFWLRQRI
URWDWLRQ
,QYHUW
6NLSIUHTXHQF\
EDQGV
6HWSRLQWIRU
PRWRUFRQWURO
)URP
VHWSRLQW
VRXUFH
6SHHG
OLPLWDWLRQ
5DPS
IXQFWLRQ
JHQHUDWRU

[
\
[
\
W
\\[[
Figure 8-46 Setpoint processing in the converter
Advanced commissioning
8.17 Setpoint calculation
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 269

Table of Contents

Other manuals for Siemens SINAMICS G110M